抄録
In order to prove the effectiveness of the developed model, reported in the first report, about dynamics of a vapor compression refrigeration cycle with zeotropic refrigerant mixtures, simulation results are compared with the experimental results obtained for R-407C (R-32/R-125/R-134a=23/25/52wt%).The simulation results are consistent well with the experimental results. As a result of the numerical analysis of dynamic characteristics of composition changing, the variation of compositions in the refrigeration cycle is caused by the variation of the existing compositions of accumulator. The time constant of the composition is approximately equal to the time constant of the pressure and the mass distribution.