超臨界二酸化炭素の冷却熱伝達に関する研究
―第2報:伝熱相関式とオイルの影響―
党 超鋲飛原 英治
著者情報
ジャーナル フリー

2003 年 20 巻 2 号 p. 175-183

詳細
抄録
The characteristics of carbon dioxide cooled under supercritical condition were investigated theoretically and experimentally. Based on the results of numerical calculation and experimental measurements described in the 1st report, a new correlation was proposed to predict the heat transfer coefficient, and the Filonenko's equation was found adequate to predict the pressure drop inside as mall seized tube. Those correlations were compared with measurement results and the deviations were found lower than ±20%. Furthermore, a compressor cycle was assembled to investigate the effect of lubricant oil on heat transfer and pressure drop. The oil content in CO2 was set to be about 0.5% during the measurements. This amount of lubricant oil was found affected the heat transfer coefficient significantly, with largest degradation of heat transfer coefficient at the pseudocritical point to nearly 50%. The effect of lubricant oil at small concentration on the pressure drop was found negligible.