In order to measure the latent heat of melting of ice slurries with various solute concentrations, an adiabatic calorimeter was constructed. Ice slurries were made from each aqueous solution of ethanol, ethylene glycol and silane coupling agent. The latent heat of melting of ice made from tap water was measured with the present calorimeter and the uncertainty of the result was one percent. Ice slurries were made both by mixing ice particles made from water with each aqueous solution and by freezing each aqueous solution with stirring in a vessel. The latent heat of melting of these ice slurries was measured with various concentrations of solution. The latent heat of melting decreased as the solute concentration or the freezing point depression increased. The latent heat of ice slurries made from ethanol or ethylene glycol aqueous solution agreed with that of ice made from pure water known already. The latent heat of melting of ice slurries made from silane coupling agent aqueous solution got smaller than that of ice made from pure water as the freezing point depression increased.