In order to find the optimum operation condition of a distributed power supply system of 30kW class micro gas turbine (MGT) and solid oxide fuel cell (SOFC) hybrid system with the combination of line electric power and supplied gas, a system analysis has been performed. In this study, an absorption chiller and a boiler were mounted to utilize the exhausted heat from the MGT/SOFC system. The time variation of energy consumption in 24 hours for house and market models was taken into consideration for the calculation of the energy saving ratio of the present system. The operation ratio defined with the ratio of power supply of MGT/SOFC system to the power required at the peak load was changed as a parameter. From the comparison with the system using line power and gas, it is found that the present system shows high energy saving ratio around 0.4 of the operation ratio, but the energy saving ratio severely decreases in the range of high operation ratio. In this study, it is revealed that the thermal storage system effectively improves the energy saving ratio especially for the house model in winter season.