伝達関数を用いた吸収冷温水機の安定性解析
-第1報:溶液循環系の伝達関数モデルと要素機器特性の影響-
藤居 達郎三宅 聡岡 雅博森 清幸
著者情報
ジャーナル フリー

2006 年 23 巻 4 号 p. 377-387

詳細
抄録
A transfer function approach is found to be a practical method for ensuring stable operation of absorption chiller-heaters. The transfer function model is based on a solution-circuit of the machine, which dominates the stability of the operation. This model includes a solution pump, a generator with an overflow weir, and a float valve. We found that the solution-circuit system is designed with the cascade control, which makes the system stable. In this construction, the float valve actuates a primary control loop, and the overflow weir actuates a secondary loop. The effects of the characteristic of the solution pump and the overflow weir are estimated by the degree of the stabilities, which are the gain margin and the phase margin. We found that the characteristic of the solution pump strongly effects the stability by enhancing the effect of the cascade control and improving the stability. So it is essential for a better stability analysis model. According to these results, the established model is useful for quantitatively predicting the stabilities of a chiller-heater in operation, and simultaneously reducing its size and improving the stability of operation. We conclude that the methodology based on transfer function can provide compact and reliable absorption chiller-heaters.