This paper aims to develop a hybrid system for snow melting and space cooling by using geothermal energy in order to improve the availability factor of the borehole heat exchanger. Based on field experiments, a feasibility evaluation of the system was performed. First, snow melting experiments using geothermal energy were performed and the comparatively good road surface situation was realized. The primary energy reduction rate over 70% was shown in comparison with the conventional snow melting system. Second, regarding a snow melting tank with the hot water piping, it was clarified that the snow melting was possible even in the low temperature water of approximately 9-10°C by using water sprinkling in the tank jointly. Finally, by supplying the space cooling and dehumidification panel with the cold through the borehole heat exchanger in summer, it was shown that the good cooling effect was obtained.