2007 年 24 巻 3 号 p. 159-166
The purpose of this research and investigation is to confirm and clarify the performance characteristics of the vapor compression refrigeration cycle based on the Ericsson Cycle (referred to hereinafter as "this cycle" in this paper). The theoretical analysis and comparison in performance of the conventional refrigeration cycle with this cycle using 12 different but typical refrigerants, produced the following essential and interesting results, i.e., (1) there are conditions for maximizing the COP of this cycle using the expansion valve, (2)both the COP and refrigeration capacity using this cycle showed improvement for all refrigerants other than R717 and R32, (3)the improvement rate for the COP and the refrigeration capacity becomes larger as the specific heat ratio at the gas outlet point of the regenerative heat exchanger becomes smaller, with the rate value differing according to the type of refrigerant.