不凍液添加水溶液の飽和プール沸騰熱伝達に関する研究
松村 邦仁神永 文人
著者情報
ジャーナル フリー

2010 年 27 巻 4 号 p. 315-325

詳細
抄録
Nucleate boiling of binary mixtures is of particular importance in a various industries. The purpose of the present study is to provide experimental data and prediction method for nucleate boiling heat transfer of anti-freeze solutions, Propylene-glycol (PG)/water and Ethylene-glycol (EG)/water. The pool nucleate boiling experiments were carried out under a saturated and atmospheric condition. The platinum wire of 0.3 mm diameter was used as the heating surface. The mole fractions of solutions are varied from 0.85 to 1. It was found that the heat transfer coefficient gradually decreases with increasing fraction of anti-freeze to water. It was also shown that a small addition of propylene-glycol and ethylene-glycol also decreases the CHF value far below that of pure water. It is concluded that the correlation proposed by Fujita for several binary mixtures can well predict the heat transfer coefficients within almost ±5% accuracy for every concentration of present anti-freeze solutions.