日本冷凍空調学会論文集
Online ISSN : 2185-789X
Print ISSN : 1344-4905
ISSN-L : 1344-4905
論文
直方型収着剤ユニットの収脱着特性
堀部 明彦春木 直人稲葉 渉
著者情報
ジャーナル フリー

2012 年 29 巻 1 号 p. 153-162

詳細
抄録

The purpose of this study is to examine the dehumidification behavior of a block type desiccant unit of organic sorbent. This unit has simple rectangular parallelepiped shape, and initial cost can be lower than the desiccant rotor. This unit will be used in batch system that one unit is used for sorption and another is used for desorption at the same time. Experimental conditions are as follows, sorption air temperature is 18 °C, sorption air relative humidity is 90%, desorption air temperature is 40°C, and desorption air relative humidity is 36%. It was found that completed time of desorption is earlier than that of sorption. As a result, sorption and desorption characteristics of the block type sorbent unit and their overall-mass-transfer coefficients are clarified.

著者関連情報
© 2012 公益社団法人 日本冷凍空調学会