日本冷凍空調学会論文集
Online ISSN : 2185-789X
Print ISSN : 1344-4905
ISSN-L : 1344-4905
論文
デシカントローターの高精度数理モデルの構築とその妥当性の検証
-処理空気が室内を循環する場合の特性解析と詳細な実験-
山口 誠一齋藤 潔
著者情報
ジャーナル フリー

2012 年 29 巻 1 号 p. 195-206

詳細
抄録

In air-conditioning field, a dehumidification has become increasingly important for human health and comfort especially in hot and humid climates. However, a conventional mechanical dehumidification with a vapor compression refrigerator has some problems. Therefore, much attention has been paid recently to a desiccant air-conditioning system as an alternative to the conventional system. In this paper, we focus on a desiccant air-conditioning system using a rotary desiccant wheel. The purpose of this study is to develop the simulation model of the desiccant wheel that can be applied to the various operating conditions. In this paper, the simulation model is validated under indoor air circulation condition by comparison with the detailed experimental results. In the model, the heat and mass transfer phenomenon in both air channel side and desiccant wall side are considered in detail. As a result, the simulation results of outlet humidity and temperature were in good agreement with the experimental results under indoor air circulation condition and then the simulation model was validated.

著者関連情報
© 2012 公益社団法人 日本冷凍空調学会
前の記事 次の記事
feedback
Top