Heat transfer from tubes has been numerically simulated in a fan coil unit for an airconditioning equipment. The array of tubes has parallel louver continuous fins, perpendicular to staggered round tubes. Quite a few of slits divide plates into many strips, which are offsetted, so that the heat transfer will be augmented from the plate to the air flow. On the other hand, the conduction of heat in the platemight be prevented with these slits. The conduction retardation due to slit is estimated, and the simulation shows that the retardation is not serious for present fins.