IEICE Transactions on Electronics
Online ISSN : 1745-1353
Print ISSN : 0916-8524
Special Section on Recent Development of Electromechanical Devices (Selected Papers from IS-EMD2007)
Effect of Back-Volume of Arc-Quenching Chamber on Arc Behavior
Ruicheng DAIDegui CHENXingwen LIChunping NIUWeixiong TONGHonggang XIANG
著者情報
ジャーナル 認証あり

2008 年 E91.C 巻 8 号 p. 1261-1267

詳細
抄録
The gas-puffer effect has important effects on the interruption capability of a molded case circuit breaker (MCCB). In this paper, on the basis of a simplified model of an arc chamber with a single break, the effect of back-volume of an arc-quenching chamber on arc behavior in an MCCB is investigated. Firstly, using a 2-D optical-fiber arc-motion measurement system, experiments are performed to study the effect of back-volume on the arc-motion and gas pressure in an arc-quenching chamber. We demonstrate that the lower back-volume of the arc-quenching chamber is, the higher the pressure and the better the arc motion will be. Then, corresponding to the above experiments, the gas pressure inside the arc-quenching chamber is calculated using the integral conservation equation. The simulation results are consistent with the experimental results.
著者関連情報
© 2008 The Institute of Electronics, Information and Communication Engineers
前の記事 次の記事
feedback
Top