環境工学
地下水利用・天井放射空調システムに関する実験的研究
−地下水汲上げ量及びシステム循環水量のPMV制御−
垂水 弘夫坂本 泰邦桑原 亮一西澤 淳岩瀬 和夫
著者情報
ジャーナル フリー

2014 年 20 巻 44 号 p. 191-195

詳細
抄録

PMV control system was applied for a ceiling radiation cooling/heating system utilizing groundwater as heat source/sink. System improvements including extension of the ceiling radiation panel and inverter control of pumps were carried out in the 2012. The research results in summertime cases are summarized below:
1) Indoor PMV values were settled in the range of 0.2-0.6 which was narrower than the previous year. 2) The power consumption of the pumps dropped to 1/3 of the previous year, and that of the whole system containing an makeup air unit dropped to 2/3.

著者関連情報