日本建築学会技術報告集
Online ISSN : 1881-8188
Print ISSN : 1341-9463
ISSN-L : 1341-9463
防火
スプリンクラー設備作動時の区画内煙性状
−クリブ火源を用いた区画内火災実験−
太田 充大宮 喜文松山 賢野秋 政希山口 純一
著者情報
ジャーナル フリー

2014 年 20 巻 45 号 p. 587-592

詳細
抄録
The smoke behaviors are simulated without the effect of the sprinkler activation by the fire safety design. As one of the reasons, the studies on smoke behavior with sprinkler activation are hardly studied. Experiments were conducted on a full-scale test using wood crib as fuel, and the following results were obtained; the heat release rate decreased by effect of water spray. But the burning was continued in some experiments. The temperature and CO2 density of the upper layer was decreased, and the lower layer was raised by effect of water spray.