IEICE Electronics Express
Online ISSN : 1349-2543
ISSN-L : 1349-2543
LETTER
An innovative method to achieve minimum tripping current conformity for type A RCCBs
Ailing LiYan HanJun Sun
著者情報
ジャーナル フリー

2015 年 12 巻 7 号 p. 20141220

詳細
抄録
This paper presents an innovative method to decrease the discreteness of minimum tripping current for type A residual current operated circuit breakers (RCCBs). Different but continuous time intervals’ detection method is proposed to identify the residual current’s type and judge whether its root mean square (RMS) value has exceeded the rated value in one cycle. That is, after the timer is started, 0–3 ms ±135° leakage current is detected, 3–7 ms ±90° is detected, 7–12 ms ±0° is detected, 3–7 ms and 12–16 ms type AC is detected. What’s more, the method is fabricated in a mixed-signal 0.5 µm CMOS process, and test results show that the type A RCCB’s tripping current variation is decreased to 2.8 mA, which greatly improves the chip’s reliability and anti-interference ability.
著者関連情報
© 2015 by The Institute of Electronics, Information and Communication Engineers
前の記事 次の記事
feedback
Top