電気学会論文誌B(電力・エネルギー部門誌)
Online ISSN : 1348-8147
Print ISSN : 0385-4213
ISSN-L : 0385-4213
論文
同一の発電機起動停止計画下での当日需給運用の最適化モデルと時系列モデルの比較検討
今中 政輝小豆澤 諒太羅 恵丹栗本 宗明杉本 重幸加藤 丈佳
著者情報
ジャーナル 認証あり

2021 年 141 巻 3 号 p. 255-263

詳細
抄録

Day-ahead unit commitment (DAUC) and intraday-optimization of electric load dispatching (IOED) are widely used to simulate power system operations with high-level renewable power integration. However, operation plans made by IOED models might be infeasible in reality, because the IOED model inputs actual renewable generation in a whole day. In order to check the feasibility, this paper compares simulation results of an IOED model with results of an intraday time-series electric load dispatching model (ITED model). Both models use the same DAUC results. The IOED model was modelled as a mixed integer linear problem, and the ITED model was modelled as a rule-based control model. Annual simulation results indicate that in terms of the supply shortage, the difference between the IOED model and the ITED model was not so large, especially for large shortages. On the other hand, operations of the pumped storage hydro were less frequent in the IOED model than in the ITED model.

著者関連情報
© 2021 電気学会
前の記事 次の記事