日本放射線技術学会雑誌
Online ISSN : 1881-4883
Print ISSN : 0369-4305
ISSN-L : 0369-4305
ノート
診断用X線領域に対する無鉛ボードの遮へい評価
加藤 洋塚田 勝三田 創吾福士 政広乳井 嘉之安部 真治木村 純一
著者情報
ジャーナル フリー

2010 年 66 巻 12 号 p. 1555-1560

詳細
抄録

For physical foundation data used in the shielding calculation of structural facilities such as a radiation room, there are air kerma transmissions concerning the thickness of shielding objects, and half value layers and tenth value layers concerning a greatly attenuated wide X-ray beam. Accordingly, we evaluated the above-mentioned items with a lead-free board, which is mixed sulfuric acid calcium and barium sulfate with equiponderance for the amount of sulfuric acid calcium included in the usual plasterboard. Permeability in NCRP Report 147 is expressed by 3 parameters, α, β and γ, and shielding objects x. It showed that it corresponds to the measurement point and permeability curve with parameters, α, β and γ obtained by nonlinear regression analysis. Furthermore, we calculated the half value layer and tenth value layer concerning the greatly attenuated wide X-ray beam. The evaluated lead-free board, used in this examination, is useful as the shielding material for the diagnosis X-ray and, moreover, the partition wall materials are hard enough, with a board that is even heavier than the usual plaster board. Besides, the use of lead-free materials is friendly to the general environment.

著者関連情報
© 2010 公益社団法人 日本放射線技術学会
前の記事 次の記事