日本冷凍空調学会論文集
Online ISSN : 2185-789X
Print ISSN : 1344-4905
ISSN-L : 1344-4905
論文
温水熱源吸収式冷凍機用再生器の性能
功刀 能文臼井 三平大内 富久福田 民雄
著者情報
ジャーナル フリー

1984 年 1 巻 2 号 p. 141-149

詳細
抄録
For 70 kW generator of absorption refrigerating machine powered by the hot water, lifted liquid rate of the bubble lift pump has a maximum value at some vapor flow rate of refrigerant and hot water inlet temperature. This is in agreement with results of small size bubble lift pump. Maximum lifted liquid rate G0 is correlated by the equation ;G0 = 5, 000σ1.5, where σ is the degree of submergence. In this case, diameter of pump tube was 41.6mm, and length of it were 1,300 and 1,500mm. The range of hot water inlet temperature was 78 - 100°C.
Multitube heat flux of first generator is about two times that of second generator at the same superheat.
著者関連情報
© 1984 公益社団法人 日本冷凍空調学会