日本冷凍空調学会論文集
Online ISSN : 2185-789X
Print ISSN : 1344-4905
ISSN-L : 1344-4905
論文
吸収冷温水機の吸収器用伝熱促進管
古川 雅裕佐々木 直栄金子 敏之野世溪 精
著者情報
ジャーナル フリー

1993 年 10 巻 2 号 p. 219-226

詳細
抄録
For the purpose of development of high performance absorption chiller/heater utilizing lithium bromide aqueous solution as working fluid, it is the most effective to improve the performance of absorber with the largest heat transfer area of the four heat exchangers.
This paper introduces two kinds of double fluted tubes for the absorber of absorption chiller/heater. Arm tube and floral tube have about 40% higter heat transfer performance than the plain tube conventionally used in absorber. The former is manufactured by double drawbench process, while the latter by single drawbench process. Therefore, floral tube is expected to realize both high heat transfer perfoemance and low cost.
著者関連情報
© 1993 公益社団法人 日本冷凍空調学会