大気汚染による冷却塔水のMアルカリ度の中和量
酒井 康行
著者情報
ジャーナル フリー

1999 年 16 巻 3 号 p. 221-228

詳細
抄録

Applying actual cooling tower water analyses together with air pollution and meteorological records to the theoretical equation calculating M-alkalinity of cooling tower water which is formulated in consideration of air pollution, capture efficiencies of typical air-conditioning cooling tower for each air pollutant have been estimated approximately as 25% for SO2, 30% for NO2, and 40% for NO. Using the equation, the method to establish adequate cycles of concentration of a cooling tower water is explained.