抄録
Experiments on evaporation for water and lithium bromide (LiBr) aqueous solution were made in a externally heated wetted-wall column under reduced pressures. For water, evaporation rate increased slightly as feed rate decreased. The heat transfer coefficients of falling film agreed with those for filmwise condensation. For LiBr solution, evaporation rate decreased and outlet temperature of LiBr solution increased as feed rate decreased.
The equations of continuity, diffusion and energy which assume that only water moves to the surface and LiBr doesn't move through falling film of LiBr solution were solved numerically. Calculated values of evaporation rate and outlet temperature of solution agreed with experimental results.
The results of this work were compared with pool boiling data reported previously, and it was shown that falling film heater is superior to pool boiling heater concerning heat transfer.