抄録
Experimental studies on heat transfer performance of absorber for lithium bromide-water absorption refrigerating machine are presented in this paper. Experimental apparatus for 35 kW evaporator and absorber, and outer grooved tubes are used.
As a result, over-al1 coefficient of heat transmission of absorber has a maximum value, in the case of heat transfer area ratio of absorber to evaporator, is about 0.8. Heat transfer rate of absorber is increased by 60% by using the outer grooved tube compared with the plane surfaced tube.