日本冷凍空調学会論文集
Online ISSN : 2185-789X
Print ISSN : 1344-4905
ISSN-L : 1344-4905
論文
ドライエア製造条件におけるデシカントロータの除湿挙動
-第1 報:ロータ回転方向湿度・温度分布の測定と考察-
綾目 久雄永坂 茂之神戸 正純辻口 拓也児玉 昭雄
著者情報
ジャーナル フリー

2013 年 30 巻 4 号 p. 353-364

詳細
抄録

Angular distributions of air humidity and temperature developed at each outlet of a desiccant rotor,which was operated under the low dew point air production condition / process configuration, were carefully measured and discussed for the help in construction of mathematical model of the desiccant rotor and verification of the simulation results in a series of our study. Measurement of the angular distributions was carried out varying the rotation speed of the rotor, regeneration air temperature and process inlet air absolute humidity. Also, humidity chart was employed to interpret the angular distribution or the change of air condition along the rotation angle. It was found that the change of dehumidification and regeneration outlet air condition along the rotation angle had almost the same feature found in the desiccant rotor used for general air-conditioning. This suggests that the conventional computational model can be essentially applied to the simulation in low dew point air production condition, except that the magnitude of adsorption heat and its dependency on the amount of adsorbed water should be correctly measured and applied to the calculation.

著者関連情報
© 2013 公益社団法人 日本冷凍空調学会
前の記事 次の記事