日本冷凍空調学会論文集
Online ISSN : 2185-789X
Print ISSN : 1344-4905
ISSN-L : 1344-4905
論文
二重効用吸収冷凍機の部分負荷特性
川上 隆一郎福知 徹改田 義雄
著者情報
ジャーナル フリー

2004 年 21 巻 3 号 p. 215-225

詳細
抄録
Simulation analysis was carried out to study the partial load characteristics of three different types of double-effect LiBr-water absorption cycle, namely series flow, parallel flow and reverse flow. A computer program was developed for this study to simulate the behavior of the absorption cycles equipped with flow rate control of absorbent, cooling water and chilling water on partial load. The effects of the flow rate control on the coefficient of performance (COP), the maximum temperature and maximum pressure were studied. The results show that not only flow rate control of absorbent is essential for high COP on the partial load, but also flow rate control of cooling water and chilling water is recommendable to save the power of pumping.
著者関連情報
© 2004 公益社団法人 日本冷凍空調学会