Nihon Yoton Gakkaishi
Online ISSN : 1881-655X
Print ISSN : 0913-882X
ISSN-L : 0913-882X
Volume 53, Issue 4
Displaying 1-3 of 3 articles from this issue
Original
  • Eisuke KAWAMURA, Akira TAKADA, Yoichiro KOJIMA
    2016 Volume 53 Issue 4 Pages 129-136
    Published: December 26, 2016
    Released on J-STAGE: March 17, 2017
    JOURNAL FREE ACCESS

    The exhaust gas of the enclosed vertical type composting facilities of 10m3 volume with a fermentation capacity of 10m3 has the quantity of heat of about 60MJ/h. We tried to recover heat of this exhaust with the plate fin type heat exchanger as heating source of water. As for the result, the water flow rate was 0.7-9l/min and temperature of the heated water was 44-34°C and the heat was used to heat the water up to 0.20MJ/min in summer, which water temperature is 29.2°C. The heat exchange efficiency converged upon approximately 90% under these conditions, and the overall heat transfer coefficient was 90W/m2·K. The water flow rate was 0.6-10l/min and temperature of the heated water was 58-29°C, and the heat was used to heat the water up to 0.55MJ/min in winter, which water temperature is 11.8°C. The heat exchange efficiency converged upon approximately 90% under these conditions, and the overall heat transfer coefficient was 95-98W/m2·K. When the exhaust temperature of the enclosed vertical type composting facility current varies periodically, the overall transfer coefficient also vary periodically.