In large transmission systems the main lines are usually so arranged by means of parallel feeders that each substation on tie main system has two or more circuits over which power may flow from the generating station. Thus, when a fault develops on one of the circuits, it may be disconnected without entirely cutting the substation of the system.
In a system in which the neutral is connected to ground through a high resistance, fault current in case of one line ground is generally smaller than normal full load current, but symmetrical three phase short circuit current and line to line short circuit current are always greater than full load current. Ordinary relay systems which are used nowaday, i. e. current balance relay, over current relay, etc. give practically satisfactory protection for short circuits.
But the author has shown that for one line ground, any relay system which is used nowaday gives no satisfactory protection. Relay which has potential and current coils solves this problem. But potential transformer of such a high tension as 110, 000, 154, 000, 220, 000 volt is practically impossible to use.
The author has heard from Mr. Seto, the Engineer of Daido Electric Power Co., that a condenser bushing of oil circuit breaker would carry sufficient charging current for relay operation, and he has also shown that induced voltage in a "coupling wire" has sufficient values in amount and phase for relay operation.
View full abstract