  • 森本 雅之
    2011 年 31 巻 6 号 p. 436-442
    発行日: 2011/06/10
    公開日: 2014/09/01
    ジャーナル フリー
    A leakage current of PWM inverter driven induction motor system is discussed. The "Integrated grounding system" is introducing in Japan because of low grounding resistance and low construction price. Though,a leakage current problem of power electronics with this grounding system exists. Leakage current is PWM frequency current,which flow throughCapacitance of insulators to the ground potential greatly increase. The reduction method of leakage current in the integrated grounding system is proposed in this paper. The proposed method is adding a return path of the leakage current to the inverter system. The effect of the proposed method is assured by the experiment. The proposed method can greatly reduce the leakage current from Integrated Grounding Terminal to the earth.