The Journal of the Institute of Electrical Installation Engineers of Japan
Online ISSN : 2188-6946
Print ISSN : 0910-0350
ISSN-L : 0910-0350
Volume 28, Issue 2
Displaying 1-19 of 19 articles from this issue
  • Hiroshi Kobayashi, Mutsumi Aoki, Hiroyuki Ukai, Hideki Hara, Hiroshiu ...
    2008Volume 28Issue 2 Pages 153-158
    Published: 2008
    Released on J-STAGE: March 10, 2015
    JOURNAL FREE ACCESS
    In some distribution lines,the voltage around the end of distribution line rises more than the regulation voltage. One of the reasons is the Ferranti effect caused by excessive amount of static capacity (SC) in high voltage (HV) consumers. In order to adjust the amount of SC, it is desirable to install the automatic power factor controller (APFC). However the APFC is not actually widespread, because its merit is not necessarily validated. In order to increase ratio of HV consumers installing the APFC, it is important to clarify merits of the APFC quantitatively. In the paper, from the result of measuring power factor etc.at receiving points in various HV consumers, the actual evaluation model of HV consumer is proposed. By using this model, the effectiveness of APFC is evaluated quantitatively. As the result, the reduction of electrical loss becomes about 2.0% of the whole electric energy in the feeder on the conventional distribution line.
    Download PDF (3334K)
feedback
Top