It is well known that the voltage transients are caused by the operation of switchgears in a power system. The voltage transients travel along the power line as a traveling-wave, and cause malfunction of electrical devices, communication system, and the operational error of control system.
The voltage transients at the making operation of switchgear were examined to get the fundamental data for considering the immunity of communication system used on a power system. However, it was difficult to observe the voltage transients using the potential transformer and the capacitance potential device, because the transients were very rapid.
Therefore, a measurement method using the coupled transmission line system is proposed to measure the high speed and high voltage transients, and the actual experimental results on the 6.9 kV power system are presented. This method enables the measurement of high speed voltage transients in out of contact with power system.
抄録全体を表示